NUTECH -INDUSTRIAL ONLINE UPS 10 KVA-60KVA
NUTECH – INDUSTRIAL Online UPS 10 kVA – 60 kVA
3-phase Input, 1-phase Output, Double Conversion, Standalone
A Transformer-based rugged UPS manufactured for tough environments
NUTECH has over 30 years of experience in providing advance power solutions for safe & managed power through its existing range of NUTECH – INDUSTRIAL Online UPS System 10 kVA – 60 kVA, 3-phase Input, 1-phase Output. NUTECH is committed to the highest standards of quality and customer satisfaction.
We response to Future Standards & Quality
NUTECH – INDUSTRIAL UPS System 10 kVA – 60 kVA UPS meets all criteria to be titled “Continuous Operation”, and is therefore a True On-line UPS System. A rugged SCR (Thyristorised) Bridge Rectifier cum Charger with Built in solid state Automatic float-cum boost Charger with Constant Voltage and Constant Current mode of Charging along with current limiting features are provided. The latest generation state-of-the-art IGBT Bridge in Inverter technology with Instantaneous Sine Wave Control & adaptive PWM technique is used. A key advantage of this technology is that no de-rating of the UPS Power is required when driving non-linear loads.
NUTECH UPS front panel is equipped with back-light Alpha-Numeric LCD Display indicating the UPS operating status and parameters of Input – Voltage, Current, Frequency, Battery – Voltage, Charging Current, Output – Voltage, Current, Frequency and other important information such as Alarms and Indications.
Isolation Transformer & EMC Standards
Due to the Double Conversation technique & Inbuilt Galvanic Isolation Transformer, (Neutral is Electrically and physically Isolated from the Input Power Circuit / Utility Neutral) which ensures no spike & surge in the output. The effective screening of Noises, Transients etc., by the ideally designed filters ensures the output is free from EMI /RFI, which complies all the EMC standards thus providing full safety to the very critical equipments.





TECHNICAL SPECIFICATION (3-ph to 1-ph UPS) | ||||||
UPS Configuration (3-ph Input & 1-ph Output) |
On-Line, Double Conversion UPS (Standalone UPS) | |||||
Output Power Rating at 0.8 p.f. | kVA | 10kVA | 15kVA | 20 kVA | 30kVA | 40kVA / 60kVA |
Dimensions (L x W x H) approx. | mm | 770 x 410 x 810 | 820 x 470 x 975 | 1000 x 610 x 1100 | ||
Input Voltage & Phase | AC | 400V (+ 20%, – 25%), 3-phase, 4-wire | ||||
Input Frequency | Hz | 50Hz (± 6%) | ||||
Nominal BATTERY Voltage | DC | 240 / 360 | 240 / 360 | 240 / 360 | 360 | 360 |
Output Voltage & Phase | AC | 230V ( ± 1%), 1-phase | ||||
Output Frequency | Hz | 50 (± 0.004) Hz | ||||
Noise Level (complies DIN 45630) | db (A) | < 40 db | ||||
Invertor Technology | Latest Microcontroller / DSP based Instantaneous Sine Wave Controlled PWM – IGBT | |||||
Waveform | Sinusoidal – True Sine Wave | |||||
Metering (LCD Display) |
Input & Output Voltage, Current, Frequency Battery Voltage & Current |
|||||
Protections & Indications | Fault trip Alarm for Single phasing, Mains failure, Mains Low & High, Battery Low & High, Inverter Under-Voltage, Over-Voltage & Over-load, Output Short-Circuit and Over Temperature. | |||||
Crest Factor | 3:1 | |||||
Harmonic Distortion at Linear Load | < 2% | |||||
Harmonic Distortion at 100% non-Linear Load (Complies EN 50091-1) | < 3% | |||||
Transient voltage Stability (Load Step 100%) |
± 3% | |||||
Overload Capability on Invertor | 125% for 10 min. 150% for 30 sec | |||||
Efficiency at Nominal Load | > 95% | |||||
Inbuilt Isolation Transformer |
100% protection is provided to critical loads by generating fresh neutral from the UPS Output Isolation Transformer. A complete Isolation between Input source & Output source. Also, handles load harmonics by Isolation Transformer |
|||||
Manuel Bypass | Manuel Bypass switch is provided for the maintenance | |||||
Communication (Optional) | RS 232 serial interface, Ethernet interface & SNMP interface | |||||
Cooling & Ambient Operating Temperature |
Forced Air, 0-40 C (Complies IPT 1001 Category B2 for Climate/Environmental) |
|||||
Immunity and RFI Protection | Complies EN 50091-2, TP-910-A90 for EMI / RFI |