Industrial Online UPS 40 kVA – 300 kVA
3-phase Input, 3-phase Output, Double Conversion, Standalone
IBGT – IGBT Energy Saving Technology with in-built Isolation Transformer UPS System
NUTECH ENGINEERS & POWER SYSTEMS PVT LTD., is a professionally managed, technologically sound company with an enviable track record of over 30 years of experience in providing advance power solutions for safe & managed power. We at NUTECH have been providing innovative & total power solutions with contemporary technology, superior performance, quality and reliability for a broad spectrum of applications, with a strong indigenous Research & Development base.
NUTECH – GREEN POWER – Energy Saving Technology, Industrial Online UPS System 40kVA – 300kVA, 3-phase Input, 3-phase Output, Double Conversion, Standalone UPS. NUTECH is committed to the highest standards of quality and customer satisfaction.
Green Power UPS Technology – High-Efficiency Design
NUTECH GREEN POWER – ENERGY SAVING TECHNOLOGY, INDUSTRIAL UPS System 40 – 300kVA significantly decreases power consumption to create an ultra-efficient backup Battery for office and Industrial application. The NUTECH GREEN POWER – Energy Saving Technology UPS is employed with a IGBT – Bridge Rectifier cum Charger with Built in solid state Automatic float-cum boost Charger with Constant Voltage and Constant Current mode of Charging along with current limiting features. This NUTECH UPS has a Unity Input Power Factor at full load, reducing the size of the Input Cables / Fuses. Low Total Input Harmonic Distortion (THDi ‹3%) reduces load pollution, increases power quality and optimises Generator sizing. Also NUTECH UPS energy-saving designs that improve operating efficiency, reduce heat generation, and consume less power than conventional UPS models.
NUTECH UPS meets all criteria to be titled “Continuous Operation”, and is therefore a True On-line UPS System. The latest generation state-of-the-art IGBT Bridge in Inverter technology with Instantaneous Sine Wave Control & adaptive PWM technique is used. A key advantage of this technology is that no de-rating of the UPS Power is required when driving non-linear loads.
NUTECH UPS front panel is equipped with back-light Alpha-Numeric LCD Display indicating the UPS operating status and parameters of Input – Voltage, Current, Frequency, Battery – Voltage, Charging Current, Output – Voltage, Current, Frequency and other important information such as Alarms and Indications.
Isolation Transformer & EMC Standards
Due to the Double Conversation technique & Inbuilt Galvanic Isolation Transformer, (Neutral is Electrically and physically Isolated from the Input Power Circuit / Utility Neutral) which ensures no spike & surge in the output. The effective screening of Noises, Transients etc., by the ideally designed filters ensures the output is free from EMI /RFI, which complies all the EMC standards thus providing full safety to the very critical equipments.





TECHNICAL SPECIFICATION (GREEN POWER UPS – ENERGY SAVER) | |||||||||||
UPS Configuration (3-ph Input & 3-ph Output) |
On-Line, Double Conversion, ENERGY SAVING UPS (Standalone UPS) | ||||||||||
Output Power Rating at 0.8 p.f. | kVA |
40kVA / 60 kVA |
80kVA | 120kVA | 140kVA | 160kVA | 200kVA | 250kVA | 300kVA | ||
Dimensions (L x W x H) approx. | mm | 1030 x 610 1250 | 1220 x 750 x 1850 | 1500 x 900 x 1750 | 1900 x 1200 x 2100 | ||||||
Input Voltage & Phase | AC | 400V / 415V (+ 20%, – 25%), 3-phase, 4-wire | |||||||||
Input Frequency | Hz | 50 Hz (± 6%) | |||||||||
Input Power Factor | p.f. | > 0.99 (Unity Power Factor) | |||||||||
Input Current Harmonics | THDi | < 5% | |||||||||
Nominal Battery Voltage | DC | 360 / 384 / 480 / 576 / 600 | |||||||||
Output Voltage & Phase | AC | 400V / 415 ( ± 1%), 3-phase | |||||||||
Output Frequency | Hz | 50 (± 0.004) Hz | |||||||||
Noise Level (complies DIN 45630) | db (A) | < 40 db | |||||||||
Convertor Technology |
IGBT Full Wave Controlled Booster Rectifier cum Charger with Built in Solid State Automatic Float-Cum Boost Charger with Constant Current Voltage mode of Charging along with Current limiting features |
||||||||||
Invertor Technology | Latest Microcontroller / DSP based Instantaneous Sine Wave Controlled PWM – IGBT | ||||||||||
Waveform | Sinusoidal (True Sine Wave) | ||||||||||
Metering (LCD Alpha-Numeric Display) |
Input & Output Voltage, Current, Frequency, Battery Voltage & Current | ||||||||||
Protections & Indications |
Fault trip Alarm for Single phasing, Mains failure, Mains Low & High, Battery Low & High, Inverter Under-Voltage, Over-Voltage & Over-load, Output Short-Circuit and Over Temperature. |
||||||||||
Crest Factor | 3:1 | ||||||||||
Harmonic Distortion at Linear Load | < 2% | ||||||||||
Harmonic Distortion at 100% non-Linear Load (Complies EN 50091-1) | < 3% | ||||||||||
Transient voltage Stability (Load Step 100%) |
± 3% | ||||||||||
Overload Capability on Invertor | 125% for 10 min. 150% for 30 sec | ||||||||||
Efficiency at Nominal Load | > 95% | ||||||||||
Inbuilt Isolation Transformer | 100% protection is provided to critical loads by generating fresh neutral from the UPS Output Isolation Transformer. A complete Isolation between Input source & Output source. Also, handles load harmonics by Isolation Transformer | ||||||||||
Manuel Bypass (Optional) | Manuel Bypass switch is provided for the maintenance | ||||||||||
Communication (Optional) | RS 232 / RS 485 serial interface, Ethernet interface & SNMP interface | ||||||||||
Cooling & Ambient Operating Temperature |
Forced Air, 0-40 C (Complies IPT 1001 Category B2 for Climate/Environmental) |
||||||||||
Immunity and RFI Protection | Complies EN 50091-2, TP-910-A90 for EMI / RFI |